Medium voltage switchgear (MV) type Rotoblok

The subject of this document is a ROTOBLOK type state-of-the-art, indoor medium voltage switchgear intended for distribution of three-phase alternating current with a frequency of 50 Hz, at a rated voltage up to 24 kV, in industrial and commercial power sector distribution grids. The switchgears are configured from standard single bays with varied equipment. The information and technical data specified herein enable the designer to assemble a switchgear from typical modules. In case bays with equipment not specified herein or with changed dimensions are needed, the scope of equipment should be arranged with the manufacturer.

Czytaj wiecej >

14 days return

Support: +48 538 209 447

×
Dane wejściowe dla symulatora rat
cena jednostkowa
ilość jednostek

Oblicz ratę!

Ask about price

Ask about product price

Medium voltage switchgear (MV) type Rotoblok

Medium voltage switchgear (MV) type Rotoblok


The subject of this document is a ROTOBLOK type state-of-the-art, indoor medium voltage switchgear intended for distribution of three-phase alternating current with a frequency of 50 Hz, at a rated voltage up to 24 kV, in industrial and commercial power sector distribution grids. The switchgears are configured from standard single bays with varied equipment. The information and technical data specified herein enable the designer to assemble a switchgear from typical modules. In case bays with equipment not specified herein or with changed dimensions are needed, the scope of equipment should be arranged with the manufacturer.

Please fill below informations. Customer service will contact with You soon as is possible.

* Required fields

Cancel or 

Description:

The switchgear is certified by the Electrotechnical Institute.

Electrical data:
  Rotoblok 17,5kV Rotoblok 24
Rated network voltage 15 kV 20 kV
Highest device voltage 17,5 kV 24 kV
Rated frequency / number of phases 50 Hz / 3
Rated short-time network frequency
withstand voltage
55 kV / 63 kV 50 kV / 60 kV
Rated withstand lightning surge voltage 1,2/50 μs 95 kV / 110 kV 125 kV / 145 kV
Continuous rated current 630 A / 1250 A 630 A - 1250 A
Rated short-time withstand current 16 kA (1s) 16 kA (1s)
Rated peak withstand current 40 kA 40 kA
IAC internal arc resistance classification AF up to 16 kA (1s)
IP protection rating IP4X
Service conditions:
Ambient temperature
- peak short-time
+ 40°C
- highest day average
+ 35°C
- highest annual average
+ 20°C
- lowest long-term
- 25°C1)
Relative humidity of air
- highest day average
95%
- highest month average
90%
- highest day average vapour pressure
2,2 kPa
- highest month average vapour pressure
1,8 kPa
Atmosphere at the place of installation no significant contamination with salt, vapour,
dust, smoke, flammable or corrosive gasses and
lack of icing, frosting and dewing
Installation altitude up to 1000 m asl2)
Vibrations vibrations caused by external factors
or earthquakes negligible

Note:
*1) Unless the manufacturer of instrumentation & control and protection devices has specified otherwise.
*2) If the switchgear installation altitude is higher than 1000 m ASL should corrected by an indicator in accordance with the guidelines of item 2.2.1 of the PN-EN 62271-1 standard.

Rated power of transformers that can be connected and disconnected using GTR 2V disconnectors, depending on voltages on the MV side:
Rated network voltage Rated current Max. transformer power
6 kV 60,6 A 630 kVA
10 kV 57,7 A 1000 kVA
15 kV 48,1 A 1250 kVA
20 kV 46,2 A 1600 kVA

In case of transformers with higher powers please contact the switchgear manufacturer.
In Rotoblok type switchgear typical fuse links are used acc. to the IEC 282-1, DIN 43625 standard, with thermal protection.